Modbus Register Map - APM Power
Input Registers
Use Function Code 4
The Input registers show the displayed value for each parameter, scaled by the APM-PWR configured unit.
- Example: APM-PWR is configured to measure V and Kva:
- Parameter No. 1 (L1 to L2 Voltage) returned “415” should be read as a value of 415V
- Parameter No. 5 (L1 Apparent Power) returned “8.7” should be read as a value of 8.7kVA
Param No |
Address |
Type |
Details |
|---|---|---|---|
0 |
0 |
32bit Float |
Frequency |
1 |
2 |
32bit Float |
L1 to L2 Voltage |
2 |
4 |
32bit Float |
L1 to N Voltage |
3 |
6 |
32bit Float |
L1 Current |
4 |
8 |
32bit Float |
L1 Active Power |
5 |
10 |
32bit Float |
L1 Apparent Power |
6 |
12 |
32bit Float |
L1 Reactive Power |
7 |
14 |
32bit Float |
L1 Current Phase Angle |
8 |
16 |
32bit Float |
L1 Power Factor |
9 |
18 |
32bit Float |
L1 Voltage THD |
10 |
20 |
32bit Float |
L1 Current THD |
11 |
22 |
32bit Float |
L1 Max Load |
12 |
24 |
32bit Float |
L1 to L2 Voltage Phase Angle |
13 |
26 |
32bit Float |
L2 to L3 Voltage |
14 |
28 |
32bit Float |
L2 to N Voltage |
15 |
30 |
32bit Float |
L2 Current |
16 |
32 |
32bit Float |
L2 Active Power |
17 |
34 |
32bit Float |
L2 Apparent Power |
18 |
36 |
32bit Float |
L2 Reactive Power |
19 |
38 |
32bit Float |
L2 Current Phase Angle |
20 |
40 |
32bit Float |
L2 Power Factor |
21 |
42 |
32bit Float |
L2 Voltage THD |
22 |
44 |
32bit Float |
L2 Current THD |
23 |
46 |
32bit Float |
L2 Max Load |
24 |
48 |
32bit Float |
L1 to L3 Voltage Phase Angle |
25 |
50 |
32bit Float |
L3 to L1 Voltage |
26 |
52 |
32bit Float |
L3 to N Voltage |
27 |
54 |
32bit Float |
L3 Current |
28 |
56 |
32bit Float |
L3 Active Power |
29 |
58 |
32bit Float |
L3 Apparent Power |
30 |
60 |
32bit Float |
L3 Reactive Power |
31 |
62 |
32bit Float |
L3 Current Phase Angle |
32 |
64 |
32bit Float |
L3 Power Factor |
33 |
66 |
32bit Float |
L3 Voltage THD |
34 |
68 |
32bit Float |
L3 Current THD |
35 |
70 |
32bit Float |
L3 Max Load |
36 |
72 |
32bit Float |
Internal Temperature |
37 |
74 |
32bit Float |
Active Energy |
38 |
76 |
32bit Float |
Apparent Energy |
39 |
78 |
32bit Float |
Reative Energy |
40 |
80 |
32bit Float |
Total Active Power |
41 |
82 |
32bit Float |
Total Apparent Power |
42 |
84 |
32bit Float |
Total Reactive Power |
43 |
86 |
32bit Float |
All phase power factor |
Coil Registers
Use Function Code 1
- Alarm Status is :
- 1= Alarm Active
- 0= Alarm Inactive
Param No |
Address |
Type |
Details |
|---|---|---|---|
0 |
0 |
1bit |
Alarm 1 status |
1 |
1 |
1bit |
Alarm 2 status |
2 |
2 |
1bit |
Alarm 3 status |
3 |
3 |
1bit |
Alarm 4 status |
4 |
4 |
1bit |
Alarm 5 status |
5 |
5 |
1bit |
Alarm 6 status |
6 |
6 |
1bit |
Alarm 7 status |
7 |
7 |
1bit |
Alarm 8 status |
8 |
8 |
1bit |
Alarm 9 status |
9 |
9 |
1bit |
Alarm 10 status |
Modbus Sentence Protocol
The registers are implemented as 32 bit floats utilizing two 16 bit words. The most significant word is sent first. Each 16 bit word is sent as two 8 bit bytes, the most significant is sent first.
Error Codes
Code |
Error Codes |
|---|---|
1 |
Unsupported Function |
2 |
Illegal Data Address |